Figure 5. Liquid Line Temperature POWER SAVE P.O. Box 880, Cottage Grove, OR. 97424 1-541-942-5560, FAX 1-541-942-4682 Figure 5. Liquid Line Temperature
This chart clearly shows the benefit of the LPA Retrofit in lower condensing temperatures with the liquid temperature dropping 30F from 92F to 62F compared with the w/o LPA range of 91F to 96F. This effectively increases the system capacity as the R-22 refrigeration effect alone increases by approximately 0.5% per degree in this temperature range. Also comparing the liquid temperature measurements with the SCT shows approximately 10F of subcooling out of the condenser. |
|
|
|